Input/Output device EKS-4001 Type: Input/output line element Purpose: The Input/Output devices EKS-4001 are designed to start (using of relay contact) after a signal given by the control panel the alarm and other fire-protection devices, such as: signaling devices, fire dampers, fire-protection doors etc. It makes possible to control of efficiency and correctly operation of controlled unit. They have additional inputs to supervising of several devices or installations not co-operated with control. Co-operation: Fire alarm control panels POLON 4200, POLON 4800, POLON 4900 and POLON 4500. Certificate: CNBOP 1438/CPD/0071 Technical data: - power supplyfrom fire alarm control panel - current consumption form detector line145μA - outputs number1 (load capacity 2A/30V) - inputs number2 - operation temperature-25ºC ÷ +55ºC - caseEKS elements are installed in 1xEKS, 2xEKS or 4xEKS case (ordered separately)