UCS 4000 - Universālais vadības bloks

675.86
(Ieskaitot nodokli)
UCS 4000
1 prece(s)
+

Purpose:

Universal control unit UCS 4000 is microprocessor unit designed to activate fire protection equipment like natural smoke and heat exhaust units gravitational as well as mechanical and daily ventilation.

Universal control unit can operate as an individual one-zone control panel or as an addressable control element installed in control panels’ detection lines range POLON 4000.

Functionality

Control panel USC 4000 enables:

-     fire detection (smokiness);

-     automatic or manual activation of fire protection equipment that is installed with exhausting systems;

-     acoustic and optical indication of mode of operation (alarm, fault, block, test);

-     activation automatic control of fire protection equipment (servo-motors, electromagnets, exhaust fans, etc.);

-     self automatic control;

-     basic information transmission to master systems (POLON 4000, IGNIS 1000 or other) concerning fire alarm, fault, test, activation of fire protection equipment.

Control panel can operate in the following modes:

-     quiescent with the possibility of activation daily ventilation function,

-     fire alarm – activation of fire protection equipment,

-     fault,

-     block,

-     test.

 Certificate:                

CNBOP 2209/2006

Technical data:

Supply voltage                                                                       230 V +10% -15%/50 Hz
Source of standby supply battery                                       2 x 12V/7Ah
Current value available from supply device                     3,2 A    
Main relay P1 (potential):                                                    
- output voltage                                                                      24 V DC +15% -25%
- output current                                                                      2 A (3A for up to 30 minutes)
Additional relays P2, P3 (non-potential):
- current-carrying capacity                                                   1A/24V DC
Alarm devices’ relay (potential):
- output voltage                                                                      24VDC +15% -25%
- output current                                                                      0,5 A
Conventional detectors line:
- max number of detectors range 40 in the line              32
Operating temperature range                                             -10ºC…+55 ºC
Case tightness                                                                      IP44
Dimensions                                                                           400 x 300 x 130 mm