Purpose:
The PO-62 manual call point is designed for manual activation of smoke flaps. It is part of the PO-6x series, which allows for manual initiation of smoke extraction systems in emergency situations. The PO-62 features fire signaling and is equipped with a reset switch for added safety and convenience. These manual call points are suitable for both surface-mounted and flush-mounted indoor installations.
Operation Principle:
Activation of the smoke cleaning button occurs by striking or firmly pressing the protective glass, which, once displaced, provides access to the activation switch. Pressing this button sends a signal to the smoke extraction control panel, which then activates the fire alarm indication (flashing red LED). The reset of the fire state is performed with a special key, which returns the protective glass to its normal position. The PO-62 is equipped with a reset switch, allowing the smoke flap servomotor to return to its ready position.
Co-operation:
The manual call points operate with the UCS-4000 system.
Certificate: CNBOP 2209/2006
Case tightness | IP 30 |
Hole dimensions for in-plaster attachment | Φ78 x 30 mm |
Case colour | Orange |
Section of installation wires, mm² | max. 1 |
Wire reserve for connection, cm | 15 |
Operating temperature range, °C | -25 to +55 |
Overall dimensions, mm | 102.5 x 98 x 45.5 |
Weight, g | max. 220 |